4.12 Control parameters
For the monitoring of the system bus and the display of the internal states, two con-
trol parameters are provided. There is a report of the system bus state and a report o
the CAN state via two actual value parameters.
The parameter
Node-State 978 gives information about the Pre-Operational, Opera-
tional, Stopped state. A PDO transfer is only possible in the Operational state. The
state is controlled by the system bus master (PLC / PC / frequency inverter) via NM
telegrams.
The parameter
CAN-State 979 gives information about the state of the physical layer.
If there are transmission errors, the state chan
es from OKAY to WARNING until the
cancellation of the communication with BUS-OFF. After BUS-OFF, the CAN controller is
automatically re-initialized and the system bus started again.
Note: If the BUS-OFF state occurs, the frequency inverter breaks down with
"F2210 BUS-OFF".
After Bus-OFF, the system bus in the frequency inverter is completely reinitialized.
There is a new boot-up messa
e from the subscriber and an emer
ency tele
ram with
the Bus-OFF message is transmitted. The change of state of the subscriber to Opera-
tional is done by the Start-Remote-Node tele
ram cyclically sent by the system bus
master.
Actual values of the system bus
No. Description Display
978 Node-State 1 - Pre-Operational
2 - Operational
3 - Stopped
979 CAN-State 1 - OKAY
2 - WARNING
3 - BUS-OFF