5 Control inputs and outputs
5.1 Analog input EM-S1INA
5.1.1 General
The analog input of the EM-IO-02 expansion module can optionally be confi
g
ured as a
voltage or a current input. Parameterization of the input signal is done by the defini-
tion of a linear characteristic and assignment as a
reference value source
(can be selected via the parameter
Reference frequency source 475),
reference percentage source
(can be selected via the parameter
Reference percentage source 476),
actual percentage source
(can be selected via the parameter
Actual percentage source 478, in configura-
tion x11) or
limit value sources
(can be selected via the parameter
Limit Source 734…737).
5.1.2 Configuration voltage/current input
The analog input of the EM-IO-02 expansion module has been configured in the fac-
tory setting for a voltage signal of +/- 10 V.
Switch S3 enables the switch-over of the operation mode for an analo
g
current si
g
nal
of +/-20 mA.
S3
X410A
S2
X
410B
S1
ON
ON
ON
Operation mode – switch S3 Function
OFF - Voltage input OFF (to the right) –
analog input EM-S1INA is configured for a
voltage signal.
ON - Current input ON (to the left) –
analog input EM-S1INA is configured for a
current signal.
Note: With the two switches S1 and S2, the bus connection of the system bus
interface is configured (refer to chapter "System Bus Interface").